Harmonics mitigation and power factor correction with a modern three-phase four-leg shunt active power filter

Abdalla, Izzeldin Idris Abdalla and Kondapalli, K. S. Rama Rao. and Nallagownden, N. Perumal. (2010) Harmonics mitigation and power factor correction with a modern three-phase four-leg shunt active power filter. In: 2010 IEEE International Conference on Power and Energy (PECon), Nov 29-Dec 1, Kuala Lumpur, Malaysia.

[thumbnail of 2010_Nov_29-Dec_1_-_IEEE_PECon2010_-_IOT-_IPFC.pdf] PDF
2010_Nov_29-Dec_1_-_IEEE_PECon2010_-_IOT-_IPFC.pdf
Restricted to Registered users only

Download (424kB) | Request a copy

Abstract

In this paper a compensating system using four-leg shunt active power filter (SAPF) in a three-phase four-wire distribution network which will be able to mitigate harmonics, absorb or generate reactive power, and improve the power factor on supply side, is presented. Two control approaches based on p-q theory and load current detection using phase locked loop (PLL) are proposed. To validate the compensation performance of SAPF the distribution network with nonlinear loads is simulated using MATLAB/Simulink software. Simulation results have proved and validated the performance of SAPF minimizing the total harmonics distortion (THD) and neutral current.

Item Type: Conference or Workshop Item (Paper)
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Departments / MOR / COE: Departments > Electrical & Electronic Engineering
Depositing User: Assoc Prof Dr K. S. Rama Rao
Date Deposited: 26 Sep 2011 09:36
Last Modified: 19 Jan 2017 08:23
URI: http://scholars.utp.edu.my/id/eprint/4380

Actions (login required)

View Item
View Item