Logo

Operation and Performance of a Thermal Energy Storage System: A Case Study of Campus Cooling using Co-generation Plant.

Abd Majid, Mohd Amin and Nasir Rashid, Meseret and Waluyo, Joko (2012) Operation and Performance of a Thermal Energy Storage System: A Case Study of Campus Cooling using Co-generation Plant. Energy Procedia, 14 . pp. 1280-1285. ISSN 1876-6102

[img] PDF - Published Version
Restricted to Registered users only

378Kb

Abstract

The paper presents the study on operation and performance of thermal energy storage (TES) system. The TES system is installed at a cogeneration plant for campus cooling. Operating data from 2006 until 2009 were anlaysed to evaluate the operating modes, half-cycle figure of merit (FOM) and thermocline performance of the TES system. The findings indicate that the TES system was operated based on partial mode strategy. The average half-cycle FOM evaluated for charging and discharging are 0.47 and 0.67 respectively. The thermocline thickness estimated is 1.5 m. The temperature distribution profiles indicate that the TES functioned as stratified TES.