Computer simulation investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper Balconies

Nasif, M.S. and Hasnain, S.A. and Pao, W. and Al-Waked, R. (2014) Computer simulation investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper Balconies. In: UNSPECIFIED.

Full text not available from this repository.
Official URL: https://www.scopus.com/inward/record.uri?eid=2-s2....

Abstract

This paper performed the effect of installing channel screen on smoke contamination in the presence of 0.5 m deep down stand in a fire compartment. The results are then compared with smoke contamination occurrence when the channel screens were removed. The results showed that there will be 96 increase in upper balconies smoke contamination in an atrium when no channel screens at fire compartment opening are used. This work provides new correlation obtained from numerical study which can predict the smoke contamination height in upper balconies of the atrium in the presence of 0.5 m down stand and no channel screens. The proposed correlation will be useful design tool for building designer to design safe shopping malls (atrium). © 2014 Owned by the authors, published by EDP Sciences.

Item Type: Conference or Workshop Item (UNSPECIFIED)
Impact Factor: cited By 0
Uncontrolled Keywords: Computer simulation; Contamination; Design, Building designers; Design tool; Fire compartments; New correlations, Smoke
Depositing User: Ms Sharifah Fahimah Saiyed Yeop
Date Deposited: 29 Mar 2022 05:02
Last Modified: 29 Mar 2022 05:02
URI: http://scholars.utp.edu.my/id/eprint/32253

Actions (login required)

View Item
View Item